Rooftop package unit changeout on a flat commercial roof — pics from today

Wrapped up a Carrier 48TCA036 to 48TCEA042 changeout today. 3.5-ton to a 3.5-ton, but the old unit was a 1998 and efficiency was in the low 10s. New unit is 15.2 SEER2.

Crane pick was the fun part — the building has no rooftop access for equipment. Had to work with a 40-ton crane from the parking lot and do the pick blind over the parapet. Six inches of clearance on the drop.

Lineset was salvageable (3/8 liquid, 7/8 suction, 65-foot run — within spec for the new unit). Did a triple evacuation to 200 microns. Nitrogen-charged the new unit from the Schrader. Startup temp diff was 22°F. Good install.

💬 4 replies

Log in or sign up to leave a reply.

u/duct_doctor •

Did you have to adapt the curb or was the footprint close enough? Carrier made some dimensional changes around 2010 that make direct curb drops tricky on older builds.

108
u/boiler_bill •

What did the electricity bill look like before vs after? SEER 10 to SEER 15 is a meaningful efficiency jump on a commercial building. Did the customer do any kind of energy audit before the changeout?

94
u/minisplit_mike •

Triple evacuation to 200 microns — that's how it should be done. I still see guys pulling to 500 microns and calling it a day. Good habits.

24
u/freon_frank •

Six inches of clearance on a blind pick. That's why crane operators get paid what they get paid. Nice install — 22°F temp split on startup is solid. What was your superheat and subcooling on first startup?

6