Annual inspection findings I see most often, ranked, after 200 inspections this year Inspection
Ran the numbers on this year's inspection reports. Here is what actually gets written up, in order of frequency.
1. Documentation missing or wrong. By a mile. No record of completion, no as-builts, sequence of operation that does not match the installed system. Roughly 60% of buildings.
2. Devices obstructed. Storage stacked in front of pull stations, a strobe behind a new partition, smoke detectors covered from a renovation and never uncovered. About 40%.
3. Batteries past date or undersized. Either the date is expired or somebody added devices and never recalculated the standby load. About 30%.
4. Sensitivity out of range. Addressable systems report this and nobody reads it. The panel has been telling you for two years.
5. Sequence of operation not tested. Everybody tests devices. Far fewer test the actual matrix — does the elevator recall work, do the dampers close, does the HVAC shut down.
The pattern in all five is that the failures are not equipment failures. The equipment mostly works. It is the paperwork, the coordination with other trades, and the things nobody looks at.