Neutral-to-ground voltage climbing through the day on one branch — 0.4V at 7am, 6.1V by 3pm Troubleshooting
Plant office wing, 120/208 wye, one 20A branch circuit feeding a row of workstations. IT is complaining about intermittent equipment resets, always in the afternoon.
Measured N-G at the receptacle:
07:00 — 0.4V
11:00 — 3.2V
15:00 — 6.1V
19:00 — 1.1V
Circuit is not overloaded. Measured 11A at peak on a 20A circuit. Insulation resistance is fine. No shared neutral on this one, it is a dedicated 12AWG homerun about 140 feet back to panel LP-2.
The daily curve says thermal to me but 11A on 12AWG should not be producing that kind of drop. What am I missing?